NEC Chapter 9 Table 8 Compliant

Single-Phase Voltage Drop Calculator

Determine voltage drop ($V_d$), percentage loss ($\%V_d$), and recommended AWG conductor size for 120V/240V single-phase systems.

Direct Calculation Formula & NEC Guidelines

Single-Phase Circular Mil ($CM$) required: CM = (2 × K × I × D) / V_d

Where K = 12.9 Ω·cmil/ft for Copper, 21.2 Ω·cmil/ft for Aluminum (at 75°C), I = Load Current (Amps), D = One-Way Distance (Feet), and V_d = Allowable Voltage Drop (Volts). Standard NEC 210.19(A) recommends max 3% voltage drop for branch circuits.

Circuit Parameters

20 A
Voltage Drop ($V_d$) 4.75 V
Drop Percentage 3.96%
NEC Status (≤3%) NON-COMPLIANT
Voltage Drop Scale Meter 3.96% of Source Voltage
0% 3% NEC Limit 10% Max

Recommended Minimum Wire Size for ≤3% Limit

Calculated Minimum Circular Mils 8,600 CM
Safe AWG Recommendation 10 AWG